Summary
Several Murrelektronik devices using Profinet are shipped with the default SNMP community names ('public' for read access and 'private' for write access). If these community strings remain unchanged in the field, an unauthenticated attacker with network access to the device can read its configuration and, depending on the writable OIDs, modify device settings.
Impact
An unauthenticated attacker with network access to an affected device can read sensitive configuration data via SNMP read access (loss of confidentiality). With write access to the 'private' community, the attacker can modify device parameters exposed via writable OIDs, which may disrupt device operation or alter the behaviour of connected industrial processes (loss of integrity and potential loss of availability).
Affected Product(s)
| Model no. | Product name | Affected versions |
|---|---|---|
| 56006 | Cube20 BN-PNIO DI8 | Murrelektronik Firmware Cube20 vers:all/* |
| 57106 | Cube20S Profinet IO Bus node | Murrelektronik Firmware Cube20 vers:all/* |
| 56526 | Cube67+ BN-PNIO | Murrelektronik Firmware Cube20 vers:all/* |
| 55153 | IMPACT67 PN DI16 M12L 4P | Murrelektronik Firmware Impact67 vers:all/* |
| 55173 | IMPACT67 PN DI16 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 55154 | IMPACT67 PN DI8 DO8 M12L 4P | Murrelektronik Firmware Impact67 vers:all/* |
| 55174 | IMPACT67 PN DI8 DO8 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 55155 | IMPACT67 PN DO16 M12L 4P | Murrelektronik Firmware Impact67 vers:all/* |
| 55175 | IMPACT67 PN DO16 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 54620 | IMPACT67 Pro PN DIO8 IOL8 M12L 4P | Murrelektronik Firmware Impact67 Pro <=V1.9.1 |
| 54630 | IMPACT67 Pro PN DIO8 IOL8 M12L 5P | Murrelektronik Firmware Impact67 Pro <=V1.9.1 |
| 55091 | Impact67 PN DI16 | Murrelektronik Firmware Impact67 vers:all/* |
| 55092 | Impact67 PN DI8 DO8/2 | Murrelektronik Firmware Impact67 vers:all/* |
| 55152 | Impact67 PN DIO12 DIO4/IOL4 M12L 4P | Murrelektronik Firmware Impact67 vers:all/* |
| 55172 | Impact67 PN DIO12 DIO4/IOL4 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 55132 | Impact67 PN DIO12 IOL4 IRT | Murrelektronik Firmware Impact67 vers:all/* |
| 55151 | Impact67 PN DIO14 DIO2/IOL2 M12L 4P | Murrelektronik Firmware Impact67 vers:all/* |
| 55171 | Impact67 PN DIO14 DIO2/IOL2 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 55131 | Impact67 PN DIO14 IOL2 IRT | Murrelektronik Firmware Impact67 vers:all/* |
| 55130 | Impact67 PN DIO16 IRT | Murrelektronik Firmware Impact67 vers:all/* |
| 55150 | Impact67 PN DIO16 M12L 4P | Murrelektronik Firmware Impact67 vers:all/* |
| 55170 | Impact67 PN DIO16 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 55094 | Impact67 PN DO16 | Murrelektronik Firmware Impact67 vers:all/* |
| 55093 | Impact67 PN DO8/2 | Murrelektronik Firmware Impact67 vers:all/* |
| 54530 | MVK MPNIO DI16 | Murrelektronik Firmware MVK vers:all/* |
| 55163 | MVK MPNIO DI16 M12L 4P | Murrelektronik Firmware MVK vers:all/* |
| 55183 | MVK MPNIO DI16 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 55516 | MVK MPNIO DI6 DO6 IOL2 IRT PP | Murrelektronik Firmware MVK vers:all/* |
| 54531 | MVK MPNIO DI8 DO8 | Murrelektronik Firmware MVK vers:all/* |
| 55339 | MVK MPNIO DI8 DO8 FSU | Murrelektronik Firmware MVK vers:all/* |
| 55164 | MVK MPNIO DI8 DO8 M12L 4P | Murrelektronik Firmware MVK vers:all/* |
| 55184 | MVK MPNIO DI8 DO8 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 54532 | MVK MPNIO DO16 | Murrelektronik Firmware MVK vers:all/* |
| 55165 | MVK MPNIO DO16 M12L 4P | Murrelektronik Firmware MVK vers:all/* |
| 55185 | MVK MPNIO DO16 M12L 5P | Murrelektronik Firmware Impact67 vers:all/* |
| 55510 | MVK PN FDI6/3 FDO2/1 DIO4 IOL2 IRT PP | Murrelektronik Firmware MVK vers:all/* |
| 5551001 | MVK PN FDI6/3 FDO2/1 DIO4 IOL2 IRT PP K | Murrelektronik Firmware MVK vers:all/* |
| 54600 | MVK Pro MPNIO DIO8 IOL8 M12L 4P | Murrelektronik Firmware MVK Pro <=V1.9.1 |
| 54610 | MVK Pro MPNIO DIO8 IOL8 M12L 5P | Murrelektronik Firmware MVK Pro <=V1.9.1 |
| 555280 | MVK+ MPNIO DI8 DI8 IRT PP | Murrelektronik Firmware MVK vers:all/* |
| 55528 | MVK+ MPNIO DI8 DI8 IRT Push Pull | Murrelektronik Firmware MVK vers:all/* |
| 55254 | MVK+ MPNIO DI8 DI8 POF IRT PP | Murrelektronik Firmware MVK vers:all/* |
| 55268 | MVK+ MPNIO DI8 DI8 Push Pull | Murrelektronik Firmware MVK vers:all/* |
| 555290 | MVK+ MPNIO DI8 DO8 IRT PP | Murrelektronik Firmware MVK vers:all/* |
| 55529 | MVK+ MPNIO DI8 DO8 IRT Push Pull | Murrelektronik Firmware MVK vers:all/* |
| 55255 | MVK+ MPNIO DI8 DO8 POF IRT PP | Murrelektronik Firmware MVK vers:all/* |
| 55269 | MVK+ MPNIO DI8 DO8 Push Pull | Murrelektronik Firmware MVK vers:all/* |
| 55283 | MVK+ MPNIO DIO8 DIO8 Push Pull | Murrelektronik Firmware MVK vers:all/* |
| 55287 | MVK-MPNIO DI8 (DI8) | Murrelektronik Firmware MVK vers:all/* |
| 55162 | MVK-MPNIO DIO12 DIO4/IOL4 M12L 4P | Murrelektronik Firmware MVK vers:all/* |
| 55182 | MVK-MPNIO DIO12 DIO4/IOL4 M12L 5P | Murrelektronik Firmware MVK vers:all/* |
| 55532 | MVK-MPNIO DIO12 IOL4 IRT | Murrelektronik Firmware MVK vers:all/* |
| 55161 | MVK-MPNIO DIO14 DIO2/IOL2 M12L 4P | Murrelektronik Firmware MVK vers:all/* |
| 55181 | MVK-MPNIO DIO14 DIO2/IOL2 M12L 5P | Murrelektronik Firmware MVK vers:all/* |
| 55531 | MVK-MPNIO DIO14 IOL2 IRT | Murrelektronik Firmware MVK vers:all/* |
| 55530 | MVK-MPNIO DIO16 IRT | Murrelektronik Firmware MVK vers:all/* |
| 55160 | MVK-MPNIO DIO16 M12L 4P | Murrelektronik Firmware MVK vers:all/* |
| 55180 | MVK-MPNIO DIO16 M12L 5P | Murrelektronik Firmware MVK vers:all/* |
| 55288 | MVK-MPNIO DIO8 (DI8) | Murrelektronik Firmware MVK vers:all/* |
| 55289 | MVK-MPNIO DIO8 (DIO8) | Murrelektronik Firmware MVK vers:all/* |
| 55556 | MVK-MPNIO F DI16/8 7/8" IRT | Murrelektronik Firmware MVK vers:all/* |
| 5555610 | MVK-MPNIO F DI16/8 7/8" IRT xT | Murrelektronik Firmware MVK vers:all/* |
| 55562 | MVK-MPNIO F DI16/8 PP | Murrelektronik Firmware MVK vers:all/* |
| 5556210 | MVK-MPNIO F DI16/8 PP xT | Murrelektronik Firmware MVK vers:all/* |
| 55557 | MVK-MPNIO F DI8/4 F DO4 7/8" IRT | Murrelektronik Firmware MVK vers:all/* |
| 5555710 | MVK-MPNIO F DI8/4 F DO4 7/8" IRT xT | Murrelektronik Firmware MVK vers:all/* |
| 55563 | MVK-MPNIO F DI8/4 F DO4 PP | Murrelektronik Firmware MVK vers:all/* |
| 5556310 | MVK-MPNIO F DI8/4 F DO4 PP xT | Murrelektronik Firmware MVK vers:all/* |
| 58841 | Xelity 10 TX IP67 M FE PN 4P | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58851 | Xelity 10 TX IP67 M FE PN 5P | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58845 | Xelity 10 TX IP67 M GE PN 4P | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58855 | Xelity 10 TX IP67 M GE PN 5P | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58821 | Xelity 4TX M GE PN | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58847 | Xelity 6TX 4PW IP67 M GE PN 4P | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58857 | Xelity 6TX 4PW IP67 M GE PN 5P | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58823 | Xelity 6TX M GE PN | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58843 | Xelity 8 +2 TX IP67 M GE PN 4P | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58853 | Xelity 8 +2 TX IP67 M GE PN 5P | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58825 | Xelity 8TX M GE PN | Murrelektronik Firmware Xelity <=V2.1.0 |
| 58827 | Xelity-16TX-M-GE-PN | Murrelektronik Firmware Xelity <=V2.1.0 |
Vulnerabilities
Expand / Collapse allAn SNMP community name is the default (e.g. public), null, or missing.
Remediation
No vendor fix is currently available for the majority of affected products.
A firmware update addressing vulnerability is planned for early 2027 for the Impact67 Pro (article numbers 54620, 54630) and MVK Pro (article numbers 54600, 54610) product variants.
Acknowledgments
Murrelektronik GmbH thanks the following parties for their efforts:
- CERT@VDE for coordination (see https://certvde.com )
- Lena Heim from Wenglor for reporting the vulnerability to Murrelektronik GmbH
Revision History
| Version | Date | Summary |
|---|---|---|
| 1.0.0 | 07/14/2026 12:00 | initial release |