Summary
The Year 2038 Problem affects systems using a 32-bit integer to represent time as the number of seconds since January 1, 1970. On January 19, 2038, at 03:14:07 UTC, the time value will exceed the maximum for a 32-bit integer, causing an overflow and resetting it to a negative number.
Impact
This could lead to some functions to work unexpected or stop working at all. This affects the devices both during runtime and after a restart.
Affected Product(s)
Model no. | Product name | Affected versions |
---|---|---|
0751-9?01 | WAGO CC100 0751-9x01 | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
0752-8303/8000-0002 | WAGO Edge Controller 0752-8303/8000-0002 | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
0750-810?/????-???? | WAGO PFC100 G1 0750-810x/xxxx-xxxx | WAGO Firmware <3.10.11 (FW22 Patch 2), Custom Firmware <03.10.11 (70) |
0750-811?-????-???? | WAGO PFC100 G2 0750-811x-xxxx-xxxx | WAGO Firmware <04.07.01 (FW29), Custom Firmware <04.07.01 (70) |
750-820?-????-???? | WAGO PFC200 G1 750-820x-xxx-xxx | Custom Firmware <03.10.11 (70), WAGO Firmware <3.10.11 (FW22 Patch 2) |
750-821?-????-???? | WAGO PFC200 G2 750-821x-xxx-xxx | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
0762-420?/8000-000? | WAGO TP600 0762-420x/8000-000x | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
0762-430?/8000-000? | WAGO TP600 0762-430x/8000-000x | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
0762-520?/8000-000? | WAGO TP600 0762-520x/8000-000x | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
0762-530?/8000-000? | WAGO TP600 0762-530x/8000-000x | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
0762-620?/8000-000? | WAGO TP600 0762-620x/8000-000x | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
0762-630?/8000-000? | WAGO TP600 0762-630x/8000-000x | Custom Firmware <04.07.01 (70), WAGO Firmware <04.07.01 (FW29) |
Vulnerabilities
Expand / Collapse allA low privileged user can set the date of the devices to the 19th of January 2038 an therefore exceed the 32-Bit time limit. This causes some functions to work unexpected or stop working at all. Both during runtime and after a restart.
Remediation
Update to Firmware 4.7.1 (FW29), Firmware 03.10.11 (FW22 Patch 2). For the latest Custom Firmware, please contact the WAGO support.
Revision History
Version | Date | Summary |
---|---|---|
1 | 04/15/2025 12:00 | Initial release. |