VDE-2020-005
Last update
05/22/2025 15:03
Published at
03/10/2020 14:17
Vendor(s)
Beckhoff Automation GmbH & Co. KG
External ID
VDE-2020-005
CSAF Document
Summary
The coupler's function could be inhibited by an attack.
Impact
The coupler's function could be inhibited by a denial of service attack. The coupler will not recover after the attack has stopped.
A reboot of the device recovers the operation.
Affected Product(s)
| Model no. | Product name | Affected versions |
|---|---|---|
| BK9000 | vers:all/* |
Vulnerabilities
Expand / Collapse all
Published
08/25/2026 10:58
Vulnerability characterization
7.5
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
This advisory characterizes the vulnerability differently from the official CVE record. For full details, please see the CSAF document.
This advisory characterizes the vulnerability differently from the official CVE record. For full details, please see the CSAF document.
Weakness
Uncontrolled Resource Consumption (CWE-400)
Summary
A Denial-of-Service vulnerability exists in BECKHOFF Ethernet TCP/IP Bus Coupler BK9000. After an attack has occurred, the device's functionality can be restored by rebooting.
References
Mitigation
Beckhoff will not change this behaviour.
Customers should configure a perimeter firewall to block traffic from untrusted networks to the device.
Acknowledgments
Beckhoff Automation GmbH & Co. KG thanks the following parties for their efforts:
- CERT@VDE for coordination (see https://certvde.com )
- Martin Menschner from Rhebo GmbH for support and efforts within coordinated disclousure.
Revision History
| Version | Date | Summary |
|---|---|---|
| 1 | 03/10/2020 14:17 | Initial revision. |
| 2 | 01/16/2025 11:00 | Fix: list of branches, typo in references url |
| 3 | 04/11/2025 09:00 | Fix: version range |
| 4 | 05/22/2025 15:03 | Fix: quotation mark |