Summary
Two vulnerabilities in the Web-Based Management (WBM) interface of WAGO CC100, PFC100 G2, PFC200 G2, TP600, Edge Controller and WP400 devices allow an authenticated low-privileged user to bypass intended privilege boundaries. The issues affect both the routing configuration functionality and the authorization model for PROFIBUS configuration management.
Impact
Successful exploitation of CVE-2026-80466 may allow a low-privileged attacker to execute commands with root privileges.
CVE-2026-88850 allows a low-privileged attacker to perform unauthorized modifications of protected PROFIBUS configuration parameters.
Affected Product(s)
| Model no. | Product name | Affected versions |
|---|---|---|
| 0750-811?-????-???? | 0750-811x-xxxx-xxxx | wago_os_linux <4.10.0 (FW32), custom wago_os_linux <4.10.0 (70) |
| 0750-821?-????-???? | 0750-821x-xxx-xxx | wago_os_linux <4.10.0 (FW32), custom wago_os_linux <4.10.0 (70) |
| 0751-9?01 | 0751-9x01 | custom wago_os_linux <4.10.0 (70), wago_os_linux <4.10.0 (FW32) |
| 0752-8303-8000-0002 | 0752-8303-8000-0002 | custom wago_os_linux <4.10.0 (70), wago_os_linux <4.10.0 (FW32) |
| 0762-340? | 0762-340x | wago_os_linux <4.10.0 (FW32), custom wago_os_linux <4.10.0 (70) |
| 0762-420?-8000-000? | 0762-420x-8000-000x | wago_os_linux <4.10.0 (FW32), custom wago_os_linux <4.10.0 (70) |
| 0762-430?-8000-000? | 0762-430x-8000-000x | wago_os_linux <4.10.0 (FW32), custom wago_os_linux <4.10.0 (70) |
| 0762-520?-8000-000? | 0762-520x-8000-000x | wago_os_linux <4.10.0 (FW32), custom wago_os_linux <4.10.0 (70) |
| 0762-530?-8000-000? | 0762-530x-8000-000x | custom wago_os_linux <4.10.0 (70), wago_os_linux <4.10.0 (FW32) |
| 0762-620?-8000-000? | 0762-620x-8000-000x | custom wago_os_linux <4.10.0 (70), wago_os_linux <4.10.0 (FW32) |
| 0762-630?-8000-000? | 0762-630x-8000-000x | wago_os_linux <4.10.0 (FW32), custom wago_os_linux <4.10.0 (70) |
Vulnerabilities
Expand / Collapse allA vulnerability in the Web-Based Management (WBM) routing configuration allows a low-privileged remote attacker to inject shell commands into routing parameters. Due to insufficient input validation, these values are stored in a configuration file and later processed by a privileged root helper script.
The Web-Based Management (WBM) authorization model does not properly enforce permissions for all PROFIBUS configuration operations. A low-privileged remote attacker can abuse an exposed configuration function to modify root-owned PROFIBUS parameters, including device addressing and SSA settings. This allows unauthorized changes to fieldbus-related configuration and violates the intended privilege boundaries within the management interface.
Remediation
Update to Firmware version 4.10.0 (FW32) or higher. For the latest custom Firmware please contact the WAGO support.
Acknowledgments
WAGO GmbH & Co. KG thanks the following parties for their efforts:
- CERT@VDE for coordination (see https://certvde.com )
- Ievgen Bondarenko for reporting
Revision History
| Version | Date | Summary |
|---|---|---|
| 1.0.0 | 23.11.2026 11:00 | Initial release. |