Summary
The Web-Based Management (WBM) of WAGOs programmable logic controller (PLC) is typically used for administration, commissioning and updates.
With special crafted requests it is possible to change some special parameters without authentication.
Impact
This vulnerability allows an attacker who has access to the WBM to prevent the loading of the runtime-application after restart of the device by sending specifically constructed requests without authentication.
Affected Product(s)
Model no. | Product name | Affected versions |
---|---|---|
750-831/xxx-xxx | BACnet/IP Controller 750-831/xxx-xxx | Firmware <=FW07 |
750-852 | BACnet/IP Controller 750-852 | Firmware <=FW07 |
750-880/xxx-xxx | BACnet/IP Controller 750-880/xxx-xxx | Firmware <=FW07 |
750-881 | BACnet/IP Controller 750-881 | Firmware <=FW07 |
750-882 | BACnet/IP Controller 750-882 | Firmware <=FW07 |
750-889 | BACnet/IP Controller 750-889 | Firmware <=FW07 |
750-885/xxx-xxx | Controller 750-885/xxx-xxx | Firmware <=FW07 |
Vulnerabilities
Expand / Collapse allImproper Authentication vulnerability in WAGO 750-8XX series with FW version <= FW07 allows an attacker to change some special parameters without authentication. This issue affects: WAGO 750-852 version FW07 and prior versions. WAGO 750-880/xxx-xxx version FW07 and prior versions. WAGO 750-881 version FW07 and prior versions. WAGO 750-831/xxx-xxx version FW07 and prior versions. WAGO 750-882 version FW07 and prior versions. WAGO 750-885/xxx-xxx version FW07 and prior versions. WAGO 750-889 version FW07 and prior versions.
Mitigation
Restrict network access to the device.
Do not directly connect the device to the internet.
Disable unused TCP/UDP ports.
Disable web-based management ports 80/443 after the configuration phase
Revision History
Version | Date | Summary |
---|---|---|
1 | 30.09.2020 13:06 | Initial revision. |
2 | 14.05.2025 14:28 | Fix: removed ia, firmware category, added distribution |