CODESYS: Development System V2.3 affected by two vulnerabilities through corrupted project files

VDE-2024-024
Last update
14.05.2025 15:00
Published at
06.05.2024 10:00
Vendor(s)
CODESYS GmbH
External ID
VDE-2024-024
CSAF Document

Summary

Local attackers can cause affected CODESYS Development System V2.3 installations to crash or execute code by opening malicious project files.

The CODESYS Development System V2.3 is an IEC 61131-3 programming tool for the industrial controller and automation technology sector. It stores the program code for the controller and its configuration in project files (*.pro).

Impact

The CODESYS Development System V2.3 allows corrupt project files to be opened after confirmation of a warning dialog so that legitimate users can possibly copy project fragments into a new project. This functionality does not sufficiently secure the loading of malicious project files and is therefore susceptible to the memory corruption vulnerabilities mentioned in the CVEs.

Affected Product(s)

Model no. Product name Affected versions
CODESYS Development System V2.3 Firmware <2.3.9.73

Vulnerabilities

Expand / Collapse all

Published
22.09.2025 14:57
Weakness
Out-of-bounds Write (CWE-787)
References

Published
22.09.2025 14:57
Weakness
Use After Free (CWE-416)
References

Mitigation

CODESYS GmbH strongly recommends only opening projects from trustworthy sources!
If the following dialog appears when opening a project, please pay attention to this warning and do not try to load the affected project:
"The project file is corrupt. Would you still like to try to load the project?
Attention! CODESYS could become unstable when loading a corrupt project file."
In addition, we recommend saving projects with password encryption, which offers even more protection against tampering of the project.

Remediation

Update the CODESYS Development System V2.3 to version 2.3.9.73.
As of this version, projects recognized as corrupt can no longer be opened with the CODESYS Development System V2.3. If the CODESYS Development System V2.3 detects that the project file has been manipulated, the user will be informed, and the loading will be terminated.

Note: CODESYS V2.3 is currently in the service phase. Please consider upgrading to CODESYS V3.
Please visit the CODESYS download area for more information on how to obtain the software update.

Revision History

Version Date Summary
1 06.05.2024 10:00 initial revision
2 14.05.2025 15:00 Fix: added distribution